Alarm history, Alarm instruction assignment, Alarm instruction tab – GE v6 User Manual

Page 99: Alarm monitor

Advertising
background image

Secure Perfect 6.1.1 User Manual

97

Alarm History

Reports Menu
The Alarm History option opens the Alarm History Report Form that allows you to create a report based
on the history of alarm activity.

Alarm Instruction Assignment

This window displays when you click Edit, allowing you to modify the list of alarm instructions assigned to
this alarm. Only alarm instructions in the operators’ facilities are available for assignment by this operator.
Select, and then click the right arrow to assign an available instruction. A maximum of six alarm
instructions can be assigned.
Select, and then click the left arrow to unassign an instruction.
Click OK to display results in the Instruction windowpane of the Alarm Form.

Alarm Instruction Tab

Use this tab to create instructions on how to react to alarms. The instructions should belong to the same
facility as the alarm with which they will be associated.

Number: Assign a number to the instruction records. The range for alarm instructions is 0 to
254 for a total of 255 instructions.

Instructions: Enter the text you want to display when the associated alarm occurs. The
instruction can be 0 to 64 alphanumeric characters in length.

Alarm Monitor

Operations Menu
The Alarm Monitor option opens the Alarm Monitor Form that allows you to monitor alarm activity. The
shortcut key combination for Alarm Monitor Form is CTRL+M.

Clicking this icon from the Secure Perfect toolbar can also access this option: