11 MANUAL CONTROL

11.4.2 Manual pulse generator operation execution procedure

The manual pulse generator operation is carried out by the following procedure.

Write the sequence program created in STEP 1 and

STEP 2 to the PLC CPU using GX Developer.

Using GX Developer, set the control data and create a

sequence program to enable/disable the manual pulse

generator operation. (Set the control data in the QD75

buffer memory using the TO command.)

One of the following two methods can be used.

<Method 1>

Directly set (write) the parameters in the QD75 using

GX Configurator-QP.

<Method 2>
Set (write) the parameters from the PLC CPU to the QD75
using the sequence program (TO command).

STEP 1

Manual pulse
generator operation
start

End of control

STEP 2

STEP 3

STEP 4

STEP 5

Issue a command to enable the manual pulse generator
operation, and input the signals from the manual pulse
generator.

End the input from the manual pulse generator,
and issue a command to disable the manual pulse

Manual pulse
generator operation
stop

STEP 6

Monitor the manual pulse generator operation.

Preparation

Refer to Chapter 5
and Section 11.4.3.

Refer to Section
11.4.4.

Set the parameters

Write the sequence program to the PLC CPU.

One of the following two methods can be used.

<Method 1>

Monitor using GX Configurator-QP.

<Method 2>
Monitor using GX Developer.

Monitoring of the
manual pulse
generator operation

Set " Cd. 20 Manual pulse generator 1 pulse input

magnification". (control data setting)

to

)

Pr.1

)

Pr.24

Create a sequence program in which the enable/disable is

(" Cd. 21 Manual pulse generator enable flag" setting.)

set for the manual pulse generator operation.

Stop operating the manual pulse generator, and write "0"

in " Cd. 21 Manual pulse generator enable flag".

Write "1" in " Cd.21 Manual pulse generator enable

flag", and operate the manual pulse generator.

REMARK

•

Mechanical elements such as limit switches are considered as already installed.

•

Parameter settings work in common for all control using the QD75.