Melsec-q, 15 troubleshooting – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 628

Advertising
background image

15 - 24

MELSEC-Q

15 TROUBLESHOOTING

Classification

of errors

Error
code

Error name

Error

Operation status at error occurrence

900

Outside unit setting
range

The set range of the basic parameter
1 "Unit setting" is outside the setting
range.

901

Outside pulse
number per rotation
range

The set range of the basic parameter
1 "No. of pulses per rotation" is
outside the setting range.

902

Outside movement
amount per rotation
range

The set range of the basic parameter
1 "Movement amount per rotation" is
outside the setting range.

903

Outside unit
magnification range

The set range of the basic parameter
1 "Unit magnification" is outside the
setting range.

904

Pulse output mode
error

The set range of the basic parameter
1 "Pulse output mode" is outside the
setting range.

905

Rotation direction
setting error

The set range of the basic parameter
1 "Rotation direction setting" is
outside the setting range.

906

Outside bias speed
range

• The set range of the basic

parameter 1 "Bias speed at start" is
outside the setting range.

• The bias speed exceeds the speed

limit.

The QD75 READY signal (X0) is not
turned ON.

910

Outside speed limit
value range

• The set range of the basic

parameter 2 "Speed limit value" is
outside the setting range.

• The value obtained by the

conversion of the speed limit value
with respect to the frequency
exceeds the maximum output
frequency of the unit.

• The speed limit value is smaller

than the OPR speed.

911

Outside acceleration
time 0 range

The set range of the basic parameter
2 "Acceleration time 0" is outside the
setting range.

912

Outside deceleration
time 0 range

The set range of the basic parameter
2 "Deceleration time 0" is outside the
setting range.

When the power is turned ON or PLC
READY signal (Y0) is turned from
OFF to ON:

QD75 READY signal (X0) is
not turned ON.

At start: The system will not operate.

920

Backlash
compensation
amount error

The value converted into pulse
number using the movement amount
per pulse is 256 pulses or more.

Parameter

921

Software stroke limit
upper limit

• In the unit of degree, the set value

of the detailed parameter 1
"Software stroke limit upper limit
value" is outside the setting range.

• In a unit other than degree, the

software stroke limit upper limit
value is smaller than the software
stroke limit lower limit value.

The QD75 READY signal (X0) is not
turned ON.