Parameter description issue 01/06 – Siemens 440 User Manual

Page 100

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

100

6SE6400-5BB00-0BP0

P0819[3]

Copy drive data set (DDS)

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 2

Calls "Copy Drive Data Set (DDS)" function.

The list of all Drive Data Sets (DDS) are shown in the opening instructions of the Parameter List (PLI).

Index:

P0819[0] : Copy from DDS
P0819[1] : Copy to DDS
P0819[2] : Start copy

Example:

Copying of all values from DDS1 to DDS3 can be accomplished by the following procedure:

P0819[0] = 0
P0819[1] = 2

P0819[2] = 1

2. DDS 3. DDS

P0005
P0291
P0300
P0304
P0305

..

..

.

P2484
P2487
P2488

..

..

.

..

..

.

..

..

.

[0]

[1]

[2]

1. DDS

1. DDS
3. DDS

Start copy

Note:

Start value in index 2 is automatically reset to "0" after execution of function.

P0820

BI: DDS bit 0

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4095:0

Selects command source from which to read Bit 0 for selecting a drive data set (DDS).

t

0

1

2

3

(0:0)

BI: DDS bit 0

P0820

(0:0)

BI: DDS bit 1

P0821

t

0

1

2

3

CO/BO: Act CtrlWd2

r0055

r0055

CO/BO: Act CtrlWd2

r0055

r0055

.04

.04

.05

.05

r0051[1]

DDS active

Selecting DDS

approx. 50 ms

approx. 50 ms

Changeover time

Changeover time

Drive running

Drive ready

t

r0051 [2]

CO: Active DDS

.01

Level

2

Level

3