Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

204

6SE6400-5BB00-0BP0

P2040

CB telegram off time

Min: 0

CStat:

CT

Datatype: U16 Unit:

ms

Def:

20

P-Group: COMM

Active: Immediately

QuickComm.: No

Max: 65535

Defines time after which a fault will be generated (F0070) if no telegram is received via the link.

The telegramm off time defines the time, within which a valid telegram must be received. If no valid telegram
is received within that time, the inverter trips with F0070.

Dependency:

Setting 0 = watchdog disabled

P2041[5] CB

parameter

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: COMM

Active: first confirm

QuickComm.: No

Max: 65535

Configures a communication board (CB).

Index:

P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4

Details:

See relevant communication board manual for protocol definition and appropriate settings.

r2050[8]

CO: PZD from CB

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: COMM

Max: -

Displays PZD received from communication board (CB).

.

.

.

r2091

r2090

[0]

r2050

[1]
[2]
[3]

[7]

PKW
PZD
STW
HSW

PZD1

STW1

PZD2

HSW

PZD3

PZD4

STW2

P2041[0]

CB telegram

CB on COM link

PZD mapping to parameter r2050

Parameter ID value
Process data
Control word

Main setpoint

CB-Frame

PKW

PZD

CB-Frame

Process data

Parameter

Index:

r2050[0] : Received word 0
r2050[1] : Received word 1
r2050[2] : Received word 2
r2050[3] : Received word 3
r2050[4] : Received word 4
r2050[5] : Received word 5
r2050[6] : Received word 6
r2050[7] : Received word 7

Note:

The control words can be viewed as bit parameters r2090 and r2091.

Restrictions:
-

If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.

-

If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transfered in the
2nd PZD-word,

-

When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).

Level

3

Level

3

Level