Siemens 440 User Manual

Page 121

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

121

P1040[3]

Setpoint of the MOP

Min: -650.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

5.00

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 650.00

Determines setpoint for motor potentiometer control (P1000 = 1).

Index:

P1040[0] : 1st. Drive data set (DDS)
P1040[1] : 2nd. Drive data set (DDS)
P1040[2] : 3rd. Drive data set (DDS)

Note:

-

If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse
direction will be inhibited by default of P1032 (inhibit reverse direction of MOP).

-

To re-enable reverse direction, set P1032 = 0.

r1050

CO: Act. Output freq. of the MOP

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: SETPOINT

Max: -

Displays output frequency of motor potentiometer setpoint ([Hz]).

P1120

f

P1080

1
0

1
0

t

t

t

DIN

BOP

USS

BOP link

USS

COM link

CB

COM link

1
0

t

P1082

P1121

P1035

P1036

P0840

-P1080

r1050

f

act

-P1082

Selection

DIN

BOP

USS control word

r2032 Bit13

USS control word

r2032 Bit14

or

P0702 = 13

(DIN2)

P0703 = 14

(DIN3)

P0719 = 0, P0700 = 1, P1000 = 1

P0719 = 1, P0700 = 2

or

P0719 = 0, P0700 = 2, P1000 = 1

P0719 = 1, P0700 = 1

P0719 = 11

or

or

P0719 = 0, P0700 = 4, P1000 = 1

P0719 = 1, P0700 = 4

P0719 = 41

or

USS on
BOP link

USS control word

r2036 Bit13

USS control word

r2036 Bit14

or

P0719 = 0, P0700 = 5, P1000 = 1

P0719 = 1, P0700 = 5

P0719 = 51

or

USS on

COM link

CB control word

r2090 Bit13

r2090 Bit14

or

P0719 = 0, P0700 = 6, P1000 = 1

P0719 = 1, P0700 = 6

P0719 = 61

or

CB

CB control word

UP button

DOWN button

MOP up

MOP down

Possible parameter settings for the selection of MOP:

Level

2

Level

3

Advertising