Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

252

6SE6400-5BB00-0BP0

r2858

BO: Nout timer 2

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Displays Not-output of timer 2 P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.

Dependency:

P2802[1] is active level for the timer.

P2859

BI: Timer 3

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

Define input signal of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863.

Dependency:

P2802[2] is active level for the timer.

P2860

Delay time of timer 3

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 9999.9

Defines delay time of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863.

Dependency:

P2802[2] is active level for the timer.

P2861 Mode

timer

3

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 13

Selects mode of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863.

Possible Settings:

0

ON delay (seconds)

1 OFF

delay

(seconds)

2 ON/OFF

delay

(seconds)

3 Pulse

generator

(seconds)

10 ON delay (minutes)
11 OFF

delay

(minutes)

12 ON/OFF

delay

(minutes)

13 Pulse

generator

(minutes)

Dependency:

P2802[2] is active level for the timer.

r2862

BO: Timer 3

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Displays output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863.

Dependency:

P2802[2] is active level for the timer.

r2863

BO: Nout timer 3

Min: -

Datatype: U16 Unit:

-

Def:

-

P-Group: TECH

Max: -

Displays Not-output of timer 3. P2859, P2860, P2861 are the inputs of the timer, outputs are P2862, P2863.

Dependency:

P2802[2] is active level for the timer.

P2864

BI: Timer 4

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 4000:0

Define input signal of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.

Dependency:

P2802[3] is active level for the timer.

P2865

Delay time of timer 4

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

-

Def:

0.0

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 9999.9

Defines delay time of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.

Dependency:

P2802[3] is active level for the timer.

Level

3

Level

3

Level

3

Level

3

Level

3

Level