Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

75

3.8 Command

source

P0700[3]

Selection of command source

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

2

P-Group: COMMANDS

Active: first confirm

QuickComm.: Yes Max: 6

Selects digital command source.

Possible Settings:

0

Factory default setting

1 BOP

(keypad)

2 Terminal
4

USS on BOP link

5

USS on COM link

6

CB on COM link

Index:

P0700[0] : 1st. Command data set (CDS)
P0700[1] : 2nd. Command data set (CDS)
P0700[2] : 3rd. Command data set (CDS)

Example:

Changing form P0700 = 1 to P0700 = 2 sets all digital inputs to default settings.

BOP

USS

BOP link

USS

COM link

P0700 = 2

Terminals

CB

COM link

Sequence control

Setpoint

channel

Motor

control

Caution:

Be aware, by changing of parameter P0700 all BI parameters are reset to the default value or modified as
listed in the table below.

If the Inverter is being controlled via the AOP, select USS (with the corresponding interface) for the
Command Source. If the AOP is connected to the BOP-Link Interface, then set Parameter P0700 to the
value 4 (P0700 = 4).

Note:

Changing this parameter sets (to default) all settings on item selected (see table).

P0700 = 0

P0700 = 1

P0700 = 2

P0700 = 4

P0700 = 5

P0700 = 6

P0701

1

0

1

0

0

0

P0702

12

0

12

0

0

0

P0703

9

9

9

9

9

9

P0704

15

15

15

15

15

15

P0705

15

15

15

15

15

15

P0706

15

15

15

15

15

15

P0707

0

0

0

0

0

0

P0708

0

0

0

0

0

0

P0731

52.3

52.3

52.3

52.3

52.3

52.3

P0732

52.7

52.7

52.7

52.7

52.7

52.7

P0733

0.0

0.0

0.0

0.0

0.0

0.0

P0800

0.0

0.0

0.0

0.0

0.0

0.0

P0801

0.0

0.0

0.0

0.0

0.0

0.0

Level

1

Advertising