Parameter description issue 01/06 – Siemens 440 User Manual

Page 128

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

128

6SE6400-5BB00-0BP0

P1082[3] Max.

frequency

Min: 0.00

CStat:

CT

Datatype: Float Unit:

Hz

Def:

50.00

P-Group: SETPOINT

Active: first confirm

QuickComm.: Yes Max: 650.00

Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. The
value set here is valid for both clockwise and anticlockwise rotation.

Futhermore, the monitoring function |f_act| >= P1082 (r0052 Bit10, see example below) is affected by this
parameter.

Index:

P1082[0] : 1st. Drive data set (DDS)
P1082[1] : 2nd. Drive data set (DDS)
P1082[2] : 3rd. Drive data set (DDS)

Example:

0

t

1

t

f_act

r0052
Bit 10

|f_act|

P1082 (f_max)

P1082

P1082 - P2162

Dependency:

The maximal value of motor frequency P1082 is limited to pulse frequency P1800. P1082 is dependent on
the derating characteristic as followed:

2 kHz

0 - 133.3 Hz

f

max

P1082

4 kHz

0 - 266.6 Hz

6 kHz

0 - 400 Hz

8 - 16 kHz

0 - 650 Hz

P1800


If closed-loop vector control (P1300 > 19) is selected, then the maximum frequency is internally limited by
the following equation:

200.00)

P0310,

5

min(P1082,

=

f

max


The resultant value is displayed in r1084 (resultant maximum frequency).

The maximum output frequency of inverter can be exceeded if one of the following is active:

(Flying restart active) :

(Slip compensation active ) :

p0310

100

r0330

100

p1336

p1082

f

f

(p1335)

f

max

,

slip

max

max

+

=

+

=

- p1335

0

- p1200

0

p0310

100

r0330

2

p1082

f

2

f

(p1200)

f

nom

,

slip

max

max

+

=

+

=

Note:

When using the setpoint source

- Analog

Input

- USS
-

CB (e.g. PROFIBUS)


The setpoint frequency (in Hz) is cyclically calculated using a percentage value (e.g. for the analog input
r0754) or a hexadecimal value (e.g. for the USS r2018[1]) and the reference frequency P2000.

If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterised with P0757 = 0 V,
P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the
analog input.

Level

1

Advertising