Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

169

P1470[3]

Gain speed controller (SLVC)

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

-

Def:

3.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 2000.0

Enters gain of speed controller for sensorless vector control (SLVC).

r1438

r1084

–

Kp

Tn

P1470 P1472

r0064

P1496 P0341 P0342

P1489

P1488

P1452

Act. frequency
from observer model

r0063

r1170

–

Precontrol

Freq. setpoint

Torque

setpoint

Droop

150 ms

r1518

P1492

r1490

0

1

0

r0079

r1508

*)

*) only active , if pre-control is enabled
(P1496 > 0)

Index:

P1470[0] : 1st. Drive data set (DDS)
P1470[1] : 2nd. Drive data set (DDS)
P1470[2] : 3rd. Drive data set (DDS)

P1472[3]

Integral time n-ctrl. (SLVC)

Min: 25

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

400

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 32001

Enters integral time of speed controller for sensorless vector control (SLVC).

Index:

P1472[0] : 1st. Drive data set (DDS)
P1472[1] : 2nd. Drive data set (DDS)
P1472[2] : 3rd. Drive data set (DDS)

P1477[3]

BI: Set integrator of n-ctrl.

Min: 0:0

CStat:

CUT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 4000:0

Selects source to read in command to enable speed controller.

Index:

P1477[0] : 1st. Command data set (CDS)
P1477[1] : 2nd. Command data set (CDS)
P1477[2] : 3rd. Command data set (CDS)

P1478[3]

CI: Set integrator value n-ctrl.

Min: 0:0

CStat:

UT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: CONTROL

Active: first confirm

QuickComm.: No

Max: 4000:0

Selects source for integral part of speed controller.

Index:

P1478[0] : 1st. Command data set (CDS)
P1478[1] : 2nd. Command data set (CDS)
P1478[2] : 3rd. Command data set (CDS)

Dependency:

In case of sensorless vector control, integrator freezing must be selected (Bit 1 "Integral freeze (SLVC)" of
P1400 has to be set) to save the integrator output.

Note:

-

If the setting command is not connected (P1477=0), a pending value is read in after pulse enable at the
end of the excitation time (P0346) and the integral component of the speed controller is set once.

-

If the P1482 (integral component of speed controller) is connected upon pulse enable, the integral
component of the controller is set to the last value prior the pulse inhibit.

-

Neither function works after flying start.

Level

2

Level

2

Level

3

Level

3