18 motorized potentiometer (mop) – Siemens 440 User Manual

Page 120

Advertising
background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

120

6SE6400-5BB00-0BP0

3.18

Motorized potentiometer (MOP)

P1031[3]

Setpoint memory of the MOP

Min: 0

CStat:

CUT

Datatype: U16 Unit:

-

Def:

0

P-Group: SETPOINT

Active: Immediately

QuickComm.: No

Max: 1

Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.

Possible Settings:

0

MOP setpoint will not be stored

1

MOP setpoint will be stored (P1040 is updated)

Index:

P1031[0] : 1st. Drive data set (DDS)
P1031[1] : 2nd. Drive data set (DDS)
P1031[2] : 3rd. Drive data set (DDS)

Note:

On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint
of the MOP).

P1032

Inhibit negative MOP setpoints

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 1

This parameter suppresses negative setpoints of the MOP output r1050.

Possible Settings:

0

Neg. MOP setpoint is allowed

1

Neg. MOP setpoint inhibited

Note:

The reversing functions (e.g. BOP-Reverse button if P0700 = 1) are not affected by the settings of P1032.
Use P1110 to fully prevent change of direction in setpoint channel.

P1035[3]

BI: Enable MOP (UP-command)

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

19:13

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source for motor potentiometer setpoint increase frequency.

Index:

P1035[0] : 1st. Command data set (CDS)
P1035[1] : 2nd. Command data set (CDS)
P1035[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.D = MOP up via BOP

P1036[3]

BI: Enable MOP (DOWN-command)

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

19:14

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source for motor potentiometer setpoint decrease frequency.

Index:

P1036[0] : 1st. Command data set (CDS)
P1036[1] : 2nd. Command data set (CDS)
P1036[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)
19.E = MOP down via BOP

Level

2

Level

2

Level

3

Level

3