Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

161

P1333[3]

Start frequency for FCC

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

10.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 100.0

Defines the FCC starting frequency as a percentage of the rated motor frequency (P0310).

When FCC is activated using P1300 = 1, then as a function of the FCC starting frequency plus hysteresis
and the actual frequency, a changeover is made with a continuous transition between the linear V/f
characteristic (P1300 = 0) and FCC (refer to the diagram).

f

FCC

f

f

FCC+Hys

FCC

V/f

1333

P

100

P0310

f

FCC

=

(

)

%

6

1333

P

100

P0310

f

Hys

FCC

+

=

+

Sw

itc

h-

ov

er

Index:

P1333[0] : 1st. Drive data set (DDS)
P1333[1] : 2nd. Drive data set (DDS)
P1333[2] : 3rd. Drive data set (DDS)

Notice:

-

A value that is excessively low can result in instability.

-

The constant voltage boost P1310 is continuously de-activated - essentially the same as when
switching-in FCC.

-

Contrary, the voltage boosts P1311 and P1312 remain active over the complete frequency range.