Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

92

6SE6400-5BB00-0BP0

ASPmax

100 %

10 V
20 mA

V
mA

x

100%

%

P0760

P0758

P0757

P0759

ASPmin

P0761

4000 h

P0761 > 0 and P0758 < 0 < P0760


The below example produces a -10 to +10 V analog input (-50 to +50 Hz) with center zero and a "holding
point" 0.2 V wide (0.1 V to each side of center).

ASPmax

100 %

10 V

V

x

100%

%

P0760

P0758

P0757

P0759

ASPmin

-10 V

P0761

4000 h

P0756 = 4 and P0761 > 0 and P0758 < 0 < P0760

Note:

P0761[x] = 0 : No deadband active.

Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC
scaling) are positive or negative respectively. However, deadband is active in both directions from point of
intersection (x axis with ADC scaling curve), if sign of P0758 and P0760 are opposite.

Min. frequency P1080 should be zero when using center zero setup. There is no hysteresis at the end of the
deadband.

P0762[2]

Delay for loss of signal action

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: TERMINAL

Active: Immediately

QuickComm.: No

Max: 10000

Defines time delay between loss of analog setpoint and appearance of fault code F0080.

Index:

P0762[0] : Analog input 1 (ADC 1)
P0762[1] : Analog input 2 (ADC 2)

Note:

Expert users can choose the desired reaction to F0080 (default is OFF2).

Level