Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
92
6SE6400-5BB00-0BP0
ASPmax
100 %
10 V
20 mA
V
mA
x
100%
%
P0760
P0758
P0757
P0759
ASPmin
P0761
4000 h
P0761 > 0 and P0758 < 0 < P0760
The below example produces a -10 to +10 V analog input (-50 to +50 Hz) with center zero and a "holding
point" 0.2 V wide (0.1 V to each side of center).
ASPmax
100 %
10 V
V
x
100%
%
P0760
P0758
P0757
P0759
ASPmin
-10 V
P0761
4000 h
P0756 = 4 and P0761 > 0 and P0758 < 0 < P0760
Note:
P0761[x] = 0 : No deadband active.
Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC
scaling) are positive or negative respectively. However, deadband is active in both directions from point of
intersection (x axis with ADC scaling curve), if sign of P0758 and P0760 are opposite.
Min. frequency P1080 should be zero when using center zero setup. There is no hysteresis at the end of the
deadband.
P0762[2]
Delay for loss of signal action
Min: 0
CStat:
CUT
Datatype: U16 Unit:
ms
Def:
10
P-Group: TERMINAL
Active: Immediately
QuickComm.: No
Max: 10000
Defines time delay between loss of analog setpoint and appearance of fault code F0080.
Index:
P0762[0] : Analog input 1 (ADC 1)
P0762[1] : Analog input 2 (ADC 2)
Note:
Expert users can choose the desired reaction to F0080 (default is OFF2).
Level