Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

228

6SE6400-5BB00-0BP0

P2222[3]

BI: Fixed PID setp. select Bit 2

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

0:0

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of fixed PID setpoint selection Bit 2

Index:

P2222[0] : 1st. Command data set (CDS)
P2222[1] : 2nd. Command data set (CDS)
P2222[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)

P2223[3]

BI: Fixed PID setp. select Bit 3

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:3

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of fixed PID setpoint selection Bit 3

Index:

P2223[0] : 1st. Command data set (CDS)
P2223[1] : 2nd. Command data set (CDS)
P2223[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)

r2224

CO: Act. fixed PID setpoint

Min: -

Datatype: Float Unit:

%

Def:

-

P-Group: TECH

Max: -

Displays total output of PID fixed setpoint selection.

Note:

r2224 = 100 % corresponds to 4000 hex

P2225[3]

Fixed PID setpoint mode - Bit 4

Min: 1

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: TECH

Active: first confirm

QuickComm.: No

Max: 2

Direct selection or direct selection + ON Bit 4 for PID setpoint.

Possible Settings:

1 Direct

selection

2

Direct selection + ON command

Index:

P2225[0] : 1st. Command data set (CDS)
P2225[1] : 2nd. Command data set (CDS)
P2225[2] : 3rd. Command data set (CDS)

P2226[3]

BI: Fixed PID setp. select Bit 4

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:4

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines command source of fixed PID setpoint selection Bit 4

Index:

P2226[0] : 1st. Command data set (CDS)
P2226[1] : 2nd. Command data set (CDS)
P2226[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)

Level

3

Level

3

Level

2

Level

3

Level

3