F0090 signal loss, encoder stop ii, F0101 stack overflow stop ii, F0221 pid feedback below the minimum value stop ii – Siemens 440 User Manual

Page 313: F0222 pid feedback above maximum value stop ii, F0422 no load applied to inverter stop ii, F0450 failure bist tests stop ii

Advertising
background image

Issue 01/06

Faults and Alarms

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

313

F0090 Signal loss, encoder

STOP II

Quit

Refer to F0001

Cause

-

encoder signal between the encoder and inverter is interrupted

-

excessively large difference between the setpoint (reference) and actual frequency

Diagnosis & Remedy

Please check the following:
-

is there an integrated encoder? If there is no integrated encoder, then set P0400 = 0 and select the
operating mode sensorless closed-loop vector control (P1300 = 20 or 22)

-

the connection between the encoder and the inverter

-

is the encoder faulty? (select P1300 = 0, operation with fixed speed, check the encoder signal in r0061)

-

increase the encoder signal threshold in P0492, P0494

F0101 Stack overflow

STOP II

Quit

Refer to F0001

Cause

-

software error or processor failure

Diagnosis & Remedy

-

carry-out self-test routines

F0221 PID feedback below the minimum value

STOP II

Quit

Refer to F0001

Cause

-

PID feedback below the minimum value P2268.

Diagnosis & Remedy

-

change value of P2268.

-

set feedback gain.

F0222 PID feedback above maximum value

STOP II

Quit

Refer to F0001

Cause

-

PID feedback above maximum value P2267.

Diagnosis & Remedy

-

change value of P2267.

-

set the feedback gain.

F0422 No load applied to inverter

STOP II

Quit

Refer to F0001

Cause

No Load is applied to the inverter.
As a result, some functions may not work as under normal load conditions.

F0450 Failure BIST tests

STOP II

Quit

Refer to F0001

Cause

Self-test routine unsuccessful (refer to fault value r0949):
-

r0949 = 1: Self-test routine for power module components unsuccessful

-

r0949 = 2: Self-test routine for closed-loop control module components unsuccessful

-

r0949 = 4: Several function tests were unsuccessful

-

r0949 = 8: Several tests carried-out at the I/O module were unsuccessful (only MICROMASTER 420)

-

r0949 = 16: Failure of the internal RAM at the switch-on test

Diagnosis & Remedy

-

the drive is functional, but several functions are not correctly executed.

-

replace the drive