Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

48

6SE6400-5BB00-0BP0

P0290

Inverter overload reaction

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

2

P-Group: INVERTER

Active: first confirm

QuickComm.: No

Max: 3

Selects reaction of inverter to an internal over-temperature.

Following physical values influence the inverter overload protection (see diagram):

-

heat sink temperature

-

junction temperature (IGBT temperature)

- inverter

I²t

A0504

A0505

A0506

F0004

F0005

Inverter overload reaction

P0290

f_pulse

control

i_max control

(U/f)

Current control

(SLVC, VC)

r0036

r0037

Heat sink

temperature

P0292

IGBT

temperature

P0292

i

2

t

P0294

Inverter monitoring

Possible Settings:

0

Reduce output frequency

1 Trip

(F0004)

2

Reduce pulse frequency and output frequency

3

Reduce pulse frequency then trip (F0004)

Notice:

P0290 = 0:
Reduction of output frequency is only effective if the load is also reduced. This is for example valid for
variable torque applications with a quadratic torque characteristic as pumps or fans.

A trip will always result, if the action taken does not sufficiently reduce internal temperature.

The pulse frequency P1800 is reduced only if higher than 2 kHz. The actual pulse frequency is displayed in
parameter r1801.

P0291[3] Inverter

protection

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

1

P-Group: INVERTER

Active: Immediately

QuickComm.: No

Max: 7

Bit 02 shows if phase loss dedection (input phase) of 3 phase inverters is enabled after factory reset.
Default setting of phase loss is disabled for FSA - FSC. FSD and greater it is enabled.

Bitfields:

Bit00 Reserved 0 NO 1 YES
Bit01 Reserved 0 NO 1 YES
Bit02 Phase loss detection enable 0 NO 1 YES

Index:

P0291[0] : 1st. Drive data set (DDS)
P0291[1] : 2nd. Drive data set (DDS)
P0291[2] : 3rd. Drive data set (DDS)

Details:

See P0290 (inverter overload reaction)