Issue 01/06 parameter description – Siemens 440 User Manual

Page 217

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

217

P2174[3]

Torque threshold M_thresh

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Nm

Def:

5.13

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 99999.00

Defines torque threshold for comparing actual torque.

+

0

1

{

0

1

SET
(Q=1) Q

RESET

(Q=0) Q

&

Entry freq. deviat

0.00 ... 20.00 [Hz]

P2163.D ( 3.00)

Hyster freq deviat

0.00 ... 10.00 [Hz]

P2164.D (3.00)

Delay_T rampUpCmpl

0 ... 10000 [ms]

P2166.D (10)

Torque threshold

0.00 ... 99999.00 [Nm]

P2174.D (5.13)

Delay time torque

0 ... 10000 [ms]

P2176.D (10)

f_act

RFG active

f_set

Ramp-up

completed

(active-high)

| M_actNoAcc |

> M_thresh

| M_act | > M_thresh

M_act | > M_thresh
M_actNoAcc | > M_thresh

Priority

1 RESET

2 SET

T 0

T 0

r2198 Bit10

r2198 Bit09

M_act

Index:

P2174[0] : 1st. Drive data set (DDS)
P2174[1] : 2nd. Drive data set (DDS)
P2174[2] : 3rd. Drive data set (DDS)

P2176[3]

Delay time for torque threshold

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for comparing actual torque to threshold.

Index:

P2176[0] : 1st. Drive data set (DDS)
P2176[1] : 2nd. Drive data set (DDS)
P2176[2] : 3rd. Drive data set (DDS)

P2177[3]

Delay time for motor is blocked

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for identification that motor is blocked.

Index:

P2177[0] : 1st. Drive data set (DDS)
P2177[1] : 2nd. Drive data set (DDS)
P2177[2] : 3rd. Drive data set (DDS)

P2178[3]

Delay time for motor pulled out

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for identification that motor is pulled out.

Index:

P2178[0] : 1st. Drive data set (DDS)
P2178[1] : 2nd. Drive data set (DDS)
P2178[2] : 3rd. Drive data set (DDS)

Level

2

Level

2

Level

2

Level

2

Advertising