Issue 01/06 parameter description – Siemens 440 User Manual

Page 213

Advertising
background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

213

P2162[3]

Hysteresis freq. for overfreq.

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

20.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 650.00

Hysteresis frequency for overfrequency-detection as illustrated in the diagram below.

0

1

{

Max. frequency

0.00 ... 650.00 [Hz]

P1082.D (50.00)

Overspd. hyst.freq

0.00 ... 650.00 [Hz]

P2162.D (20.00)

f_act > f_max

f_act

f_act > f_max

r2197 Bit06

Index:

P2162[0] : 1st. Drive data set (DDS)
P2162[1] : 2nd. Drive data set (DDS)
P2162[2] : 3rd. Drive data set (DDS)

P2163[3]

Entry freq. for perm. deviation

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

3.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 20.00

Threshold for detecting frequency deviation from setpoint as illustrated in the diagram P2164.

Index:

P2163[0] : 1st. Drive data set (DDS)
P2163[1] : 2nd. Drive data set (DDS)
P2163[2] : 3rd. Drive data set (DDS)

P2164[3]

Hysteresis frequency deviation

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

3.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10.00

Hysteresis frequency for detecting permitted deviation (from setpoint). This frequency controls bit 8 in status
word 1 (r0052) and bit 6 in status word 2 (r0053).

+

0

1

{

Entry freq. deviat

0.00 ... 20.00 [Hz]

P2163.D (3.00)

Delay_T perm. dev.

0 ... 10000 [ms]

P2165.D (10)

Hyster freq deviat

0.00 ... 10.00 [Hz]

P2164.D (3.00)

f_act

f_act == f_set

f_set

f_act == f_set

0 T

r2197 Bit07
r0052 Bit08
r0053 Bit06

Index:

P2164[0] : 1st. Drive data set (DDS)
P2164[1] : 2nd. Drive data set (DDS)
P2164[2] : 3rd. Drive data set (DDS)

P2165[3]

Delay time permitted deviation

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for detecting permitted deviation of frequency from setpoint.

Index:

P2165[0] : 1st. Drive data set (DDS)
P2165[1] : 2nd. Drive data set (DDS)
P2165[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2164.

Level

2

Level

2

Level

3

Level

2