Cooling in operation according to Remote Control setting.

Time Delay Safety Control (3 minutes)

7 minutes Time Save Control

Starting Current Control

Anti-Freezing Control

If the temperature of the indoor heat exchanger falls
continuously below 2°C (35.6°F) for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.

Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (50°F) (Recovery).

3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.

Compressor Reverse Rotation Protection Control

8 Operation Details

8.1.

Cooling Mode Operation

When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.

When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.

The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.

When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.

If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (36.5°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)

T = Intake air temperature - Indoor heat exchanger temperature

This is to protect reverse rotation of the compressor when there is a instantaneous power failure.