Cooling in operation according to Remote Control setting.

Time Delay Safety Control (3 minutes)

7 minutes Time Save Control

Starting Current Control

Anti-Freezing Control

•

If the temperature of the indoor heat exchanger falls
continuously below 2°C (35.6°F) for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.

•

Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (50°F) (Recovery).

3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.

Compressor Reverse Rotation Protection Control

8 Operation Details

8.1.

Cooling Mode Operation

•

When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.

•

When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.

•

The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.

•

When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.

•

If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (36.5°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)

▲

T = Intake air temperature - Indoor heat exchanger temperature

This is to protect reverse rotation of the compressor when there is a instantaneous power failure.