Compressor Protection Control

Automatic Fan Speed Mode

Afte

r thecompre

ssor starts for 50 se

conds but theoutdoor fan motor is still OFF, thecompre

ssor will stop and re

start

automatically. (Time Delay Safety Control is valid).

If the above phenomenon is repeated for 3 times, the compressor will stop totally.

The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.

When Automatic Fan Speed is selected at Remote Control during cooling operation.

Fan speed rotates in the range of Hi to Me.

Deodorizing Control.