14.1.1. Relationship between the condition of the air conditioner and pressure and

electric current

Cooling Mode

Heating Mode

Condition of theair

conditioner

Low Pressure

High Pressure

Electric current

during operation

Low Pressure

High Pressure

Electric current

during operation

Insufficient refrigerant
(gas leakage)

Clogged capillary tube
or Strainer

Short circuit in the
indoor unit

Heat radiation
deficiency of the
outdoor unit

Inefficient compression

Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

14.1.2. Diagnosis methods of a malfunction of a compressor and 4-way valve

Natureof fault

Symptom

Electric current during operation becomes approximately 20% lower than the normal value.

Insufficient compressing of a compressor

The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C [158 to
194°F]).

The difference between high pressure and low pressure becomes almost zero.

Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.

Locked compressor

Thecompressor is a humming sound.

Electric current during operation becomes approximately 80% lower than the normal value.

Insufficient switches of the 4-way valve

The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.