Panasonic CS-A9CKPG User Manual

Page 22

Advertising
background image

Hot Start Control

Anti Cold Draft Control

When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C (86°F) as diagram shown.

Hot Start is completed when indoor heat exchanger rises to 39°C (102.2°F) or over 4 minutes.

This operation is to prevent the Cold Draft during Heating mode operation.

The operation will start when compressor OFF (Thermo OFF) during Heating operation.

For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:

After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.

Anti Cold Draft Control will stop when:

Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)

After 30 minutes time saved control.

(refer to next page).

22

CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G

Advertising