8.12. Low outdoor ambient temperature control

A. Purpose

To protect air conditioner from damage under the low outdoor ambient temperature.

(Low outdoor ambient temperature < -10°C [14°F]).

B. During low outdoor ambient temperature control activated, other compressor & outdoor fan motor control is ignored. (Apply
to all operation modes.)

C. Basic operation

1. Protection control

Outdoor unit stop operation regardless operation mode setting.