Heating mode operation – Panasonic CS-A9CKPG User Manual

Page 21

Advertising
background image

Heating in operation according to Remote Control setting.

Time Delay Safety Control

30 minutes Time Save Control

Overload Protection Control

(b) Compressor high pressure protection

Compressor Reverse Rotation Protection Control

4-way Valve Control

Outdoor Fan Motor Control

Indoor Fan Motor Control

8.3.

Heating Mode Operation

When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.

When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.

The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.

(a) Outdoor Fan Control

If the temperature of the indoor heat exchanger rises to 51°C (123.8°F), Outdoor Fan stops.

The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C (120.2°F).

If the indoor heat exchanger becomes 65°C (149°F) or more, the compressor will stop and restart automatically.

(TimeDelay Safety Control - 4 minutes waiting).

If the compressor is operating continuously for 5 minutes or longer and temperature difference between intake air and indoor
heat exchanger is 5°C (41°F) or less for 2 minutes, compressor will stop and restart automatically.

(Time Delay Safety Control is valid).

T = Indoor heat exchanger temperature - intake air temperature.

This is to protect reverse rotation of the compressor when there is a instantaneous power failure.

4-way valve always ON during Heating operation. (Except Deicing operation)

When the unit is switched to “OFF” during Heating operation, 4-way valve stay at Heating position for 5 minutes.

When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds.

(30 seconds Forced Operation).

When compressor stops (reaches room temperature), indoor fan will stop for 1 minutes, operate for 3 minutes, if still not yet
reaches the room temperature, indoor fan Lo- for 40 sec. after that operate at SLo speed.

21

CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G