Electrical specifications, Mechanical specifications – Xantrex Technology Automatic Generator User Manual

Page 100

Advertising
background image

Specifications

A–2

975-0082-01-01

Electrical Specifications

*Limited to Class 2 levels (100 VA) as in Chapter 2, page 2–6.

Mechanical Specifications

Nominal input network voltage

15 VDC

Minimum operating network voltage

14.25 VDC

Maximum operating network voltage

15.75 VDC

Maximum operating current

200 mA @ nominal
input network voltage

Relay contact voltage rating

12 VDC, 30 VDC max.

Maximum relay current

5 A DC*

Nominal 12 V/24 V thermostat input voltage

12 VDC/24 VDC = On

Minimum 12 V/24 V thermostat input voltage

9.5 VDC

Maximum 12 V/24 V thermostat input voltage

30 VDC

Typical 12 V/24 V thermostat input current

14.6 mA @ 12 V

Nominal 12 V/24 V generator running B+ voltage

12 VDC/24 VDC= On

Minimum 12 V/24 V generator running B+ voltage

9.5 VDC

Maximum 12 V/24 V generator running B+ voltage 30 VDC

Typical 12 V/24 V generator running B+ current

14.6 mA @ 12 V

Communication physical layer

2, CAN

Communication protocol

Xanbus

Maximum cable length

130 ft. (40 m)

Dimensions

5 Ч 3 Ч 1 "

(146 Ч 95.5 Ч 37 mm)

Weight

0.5 lb. (225 g)

Mounting

4 #6 screws

Connectors

2 × Xanbus: RJ45—8 pins
20-contact pluggable connector
(Tyco Mate ’n’ Lok 2 connector)

3
4

---

3
4

---

1
2

---