Operating mode, Power save mode, Safe mode – Xantrex Technology Automatic Generator User Manual
Page 91: Operating mode –7 power save mode –7, Safe mode –7
 
Changing System Modes
975-0082-01-01
4–7
Operating mode
Characteristics
Operating mode is the default mode of the Auto Gen Start. In Operating 
mode, the Auto Gen Start communicates on the network, responds to 
signal input, and can start and stop the generator automatically. Operating 
mode includes all the AGS Modes described on page 3–9 of the 
Configuration chapter.
Whenever the Auto Gen Start is powered on, it is in Operating mode (with 
the AGS Mode in “ManualOff”).
Power Save mode
Characteristics
Power Save mode minimizes power draw by the Auto Gen Start and other 
devices on the Xanbus system. Power Save mode stops all 
communication on the network, putting the system to “sleep” until it 
receives a command to “wake up” again. In Power Save mode, the 
generator stops, and the Auto Gen Start cannot start it manually or 
automatically.
For more information about Power Save mode, see the System Control 
Panel Owner’s Guide.
Safe mode
Characteristics
Selecting Safe mode stops the generator (if it is running) and puts the 
Auto Gen Start (and every Xanbus-enabled device in power system) into 
Safe mode. While in Safe mode, the Auto Gen Start “listens” to and 
reports its status to the network. However, it will not start the generator 
manually or automatically while in Safe mode.
When to use
Before changing the “Gen Type” setting (see page 3–16), you must put 
the system into Safe mode.
Use Safe mode when adding or removing devices from the network. 
Authorized service personnel must also put the system into Safe mode 
before performing diagnostics and software upgrades.
If the Auto Gen Start is powered off while in Safe mode, it will be in Safe 
mode when it is powered on again.
Important:
If Auto Gen Start Fault 201 (“Unable to stop gen.”) is active, you
cannot put the Auto Gen Start into Safe mode. Before you can enter Safe mode, 
you must stop the generator via its external switch and clear the fault.