Gen Status

Full name

Generator Operating Status

Purpose

“Gen Status” reports the current operating state of the generator. You
cannot adjust any “Gen Status” values.

Gen Trigger

Purpose

“Gen Trigger” reports the source of the active generator start trigger. Start
triggers can include battery voltage, inverter load, battery state of charge,
thermostat triggers, or exercise period. You cannot adjust any “Gen
Trigger” va
lues.

Value

Description

On

The generator is running.

Off

The generator is not running.

Fault

A fault condition exists. The Auto Gen Start is not controlling the
generator, or the Auto Gen Start has an internal fault. If the generator
is still running in a fault state, it may be stopped at the generator or by
one of the generator’s control panels. See “AGS Mode” and
“Troubleshooting” on page 5–1.

Value

Description

NotOn

Generator is not running

LowBattV

Preset minimum battery voltage with associated time delay

CntctClosed

Activated thermostat 1 or 2

BattSOCLow

Preset minimum battery state of charge

ACIHigh

Preset maximum inverter load current

Exercise

Preset exercise period, exercise time, and exercise duration

ManualOn

Started manually using System Control Panel

ExtOnviaAGS

Started by external switch connected to Auto Gen Start

ExtOnviaGen

Started by switch connected to generator

UnableToStop

Auto Gen Start has lost control of the running generator