Installation

2–14

975-0082-01-01

Type 5

Type 5 is a three-wire StartStop configuration that uses relay 3 to provide
the preheat signal for Generac’s Guardian Diesel generators.

The wiring diagram for a Type 5 configuration is the same as a Type 4
(see Figure 2-6).

Table 2-6 Type 5 relay and timing preset configurations

Relay 1 mode

StartStop

Relay 3 mode

Preheat

Gen Run signal hold time

2 s

Preheat time

15 s

Preheat to crank delay

2 s

Crank time

15 s

Crank retry time

15 s

Shutdown bypass time

0 s

Start tries

3