Relay Timing

C–6

975-0082-01-01

The Auto Gen Start will make three attempts to stop the generator. If
the generator has still not stopped at the end of the third attempt, the
appropriate Fault will be generated.

Each stop attempt will consist of engaging the stop relay for 5 seconds
and then waiting 20 seconds before checking the state of the Gen Run
Signal to see if the stop attempt was successful.

Figure C-5 PulseStop mode timing diagram

Figure C-6 PulseStop mode Relay 1 behavior

Stop

Start

Time

Preheat

Relay1: Stop

Relay2: Start (Cranking)

Relay3: Preheat (Glow)
& Shutdown Bypass

Crank

Shutdown

Bypass