Exercise time, Relay3, Exercise time –31 relay3 –31 – Xantrex Technology Automatic Generator User Manual

Page 79

Advertising
background image

The Auto Gen Start Menu

975-0082-01-01

3–31

Exercise Time

Purpose

“Exercise Time” allows you to set the time of day that the Auto Gen Start
exercises the generator.

This setting also requires you to set an Exercise Period and an Exercise
Duration.

When to use

You must set the Exercise Time when you have set the Exercise Period
and the Exercise Duration.

Outcomes

If you have set the Exercise Time, the generator will start at that time after
being inactive for the Exercise Period.

If the Exercise Time you have set occurs during Quiet Time, the generator
will start when Quiet Time is over and run for the full amount of time you
have set for “Exercise Dur”.

Relay3

Purpose

“Relay3” sets the function of Relay 3 of the Auto Gen Start. The function
of Relay 3 affects contacts 19 and 20 of the 20-contact connector and
external wiring harness.

When to use

Selecting a value for “Gen Type” automatically configures “Relay3”.

You may have to manually set “Relay3” according to your make and type
of generator.

Important:

Ensure that you do not set Exercise Duration for longer than “Max

Run Time”. Attempting to do so will generate a warning on the System Control
Panel.

Important:

Consult your generator manual or a service representative from

your generator’s manufacturer for the recommended exercise duration.

Values

Default

12:00AM to 11:50PM (12-hour clock)
00:00 to 23:50 (24-hour clock)
(increments of 10 minutes)

9:00AM

Values

Default

NotUsed, Preheat, PreheatSDByp

NotUsed