Type 10, Type 10 –19 – Xantrex Technology Automatic Generator User Manual

Page 41

Advertising
background image

Installing the Auto Gen Start

975-0082-01-01

2–19

Type 10

Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.

Figure 2-11 Type 10 connection diagram

Table 2-11 Type 10 relay and timing preset configurations

Relay 1 mode

StartStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Shutdown bypass time

0 s

Start tries

3

18

17

START

16

14

13

12

GEN RUN SIGNAL

GROUND

STOP

Relay 1

Relay 2

5A fuse

5A fuse

AGS wiring harness

Generator wires

Complete overcurrent protection
not shown. Refer to page 2–6.