Enable temp1, Enable temp1 –15 – Xantrex Technology Automatic Generator User Manual
Page 63
 
The Auto Gen Start Menu
975-0082-01-01
3–15
Whenever the generator starts automatically in response to “Start DCV”, 
it will stop when the battery voltage reaches the Stop Battery Voltage 
(“StopBattV”) setting. If you have enabled “Stop Float” or “Stop 
Absorb”, the generator will stop when the Absorption or Float stages of 
the battery charging have begun.
Outcomes
If you set “Start DCV” too high, the generator will start more frequently 
than is convenient.
If you set “Start DCV” too low, your batteries may be damaged by 
repeated cycles of excessive discharge. The generator running time 
necessary to charge the batteries may exceed “Max Run Time”, and use 
too much fuel in the process.
Enable Temp1
Full name
Enable Thermostat 1.
Purpose
“Enable Temp1” is a changeable setting for starting the generator in 
response to a signal from a thermostat. With “Enable Temp1” set to On, 
the Auto Gen Start will start the generator to help power the furnace or the 
air conditioner.
When to use
Enable this setting if you have thermostats that control an air conditioning 
system with high power requirements.
Outcomes
If you enable this setting, the generator will start in response to a signal 
from the thermostat. Everything related to setting the temperature at 
which the air conditioning system comes on must be done on the 
thermostat. There are no thermostat temperature settings on the Auto Gen 
Start or the System Control Panel.
If you disable this setting, your air conditioning system will operate 
without automatic generator assistance. To operate your air conditioner, 
you will need to start the generator manually, or connect to another AC 
input source.
Values
Default
On, Off
Off (disabled)