Starting and stopping the generator –2, Starting and stopping the generator – Xantrex Technology Automatic Generator User Manual
Page 86
 
Operation
4–2
975-0082-01-01
Starting and Stopping the Generator
You can use the Auto Gen Start to start the generator manually (on 
demand, using the System Control Panel) and automatically (in response 
to an electrical system condition).
In general, to avoid Auto Gen Start faults, try not to combine automatic 
and external manual starts and stops. When the generator has been started 
automatically, let it stop automatically unless you encounter a situation 
when the generator must be stopped urgently. Likewise, if you have 
started the generator manually, ensure that you stop it manually (only the 
“Max Run Time” setting can automatically stop the generator after it has 
been started manually).
To set the Auto Gen Start to start and stop the generator 
automatically:
1. On the Auto Gen Start menu, highlight AGS Mode and press Enter.
2. Use the up arrow or down arrow button to select Automatic.
3. Press Enter.
The Auto Gen Start will start and stop the generator in response to the 
configurable settings you have set for battery voltage, state of charge, 
inverter load, quiet time or exercise time. Depending on conditions in 
the power system, the generator may start immediately after it is put 
in Automatic mode.
To start the generator manually:
1. On the Auto Gen Start menu, highlight AGS Mode and press Enter.
2. Use the up arrow or down arrow button to select ManualOn.
3. Press Enter.
To stop the generator manually:
1. On the Auto Gen Start menu, highlight AGS Mode and press Enter.
2. Use the up arrow or down arrow button to select ManualOff.
3. Press Enter.