Type 9, Type 9 –18 – Xantrex Technology Automatic Generator User Manual

Page 40

Advertising
background image

Installation

2–18

975-0082-01-01

Type 9

Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3. This configuration is intended for Westerbeke
generators.

Figure 2-10 Type 9 connection diagram

Table 2-10 Type 9 relay and timing preset configurations

Relay 1 mode

StartStop

Relay 3 mode

Shutdown Bypass

Gen Run signal hold time

0.5 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Shutdown bypass time

5 s

Start tries

3

18

17

START

16

14

13

12

GEN RUN SIGNAL

GROUND

STOP

20

19

PREHEAT & SHUTDOWN BYPASS

12V GENERATOR BATTERY +

Relay 1

Relay 3

Relay 2

5A fuse

5A fuse

5A fuse

AGS wiring harness

Generator wires

Complete overcurrent protection
not shown. Refer to page 2–6.