Fault Messages
975-0082-01-01
5–5
Fault Messages
When the Auto Gen Start detects a fault condition, it stops the generator. 
The red Fault light also comes on, and the System Control Panel displays 
a fault message.
The Auto Gen Start remembers the AGS Mode that it was in at the time it 
detected the fault. After you have cleared the fault, the Auto Gen Start 
returns to its last known AGS Mode.
W250
The selected value 
failed to change.
Try again.
No
You have tried to change 
the Gen Type without 
putting the system into 
Safe mode first.
Press “continue.” Put the 
system into Safe mode, 
change the Gen Type, then 
return the system to 
Operating mode.
You have tried to set the 
“Exercise Dur” for longer 
than “Max Run Time,” or 
“Max Run Time” for less 
than “Exercise Dur.”
Press “continue.” Ensure 
that “Max Run Time” is set 
for longer than “Exercise 
Dur.”
W500
Network 
connection lost. 
Check connections.
Yes
The Auto Gen Start has lost 
communications with the 
network because of a faulty 
connection or electronic 
signal disruption.
Check connection between 
the Auto Gen Start and the 
network.
W501
AGS has fixed 
memory problem 
and restored default 
settings.
No
The Auto Gen Start 
encountered an internal 
memory problem upon 
startup. To remain 
operational, the Auto Gen 
Start restored its default 
settings.
Acknowledge the warning 
and reset configurable 
settings if necessary.
Table 5-1 Auto Gen Start warning messages
Warning 
Number
Message
Self-
clearing?
Cause
Action