Installation

2–16

975-0082-01-01

Figure 2-8 Type 7, Type 8, and Type 11 connection diagram (two-wire)

Figure 2-9 Type 7 and Type 8 connection diagram (three-wire)

Table 2-8 Type 7 relay and timing preset configurations

Relay 1 mode

Run

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

20 s

Preheat to crank delay

1 s

Crank time

15 s

Crank retry time

30 s

Shutdown bypass time

0 s

Start tries

3

16

14

13

12

GEN RUN SIGNAL

GROUND

RUN

Relay 1

5A fuse

AGS wiring harness

Generator wires

Complete overcurrent protection
not shown. Refer to page 2–6.

18

17

START

16

14

13

12

GEN RUN SIGNAL

GROUND

RUN

Relay 1

Relay 2

5A fuse

5A fuse

AGS wiring harness

Generator wires

Complete overcurrent protection
not shown. Refer to page 2–6.