Crank retry time, Preheat time, Crank retry time –33 preheat time –33 – Xantrex Technology Automatic Generator User Manual

Page 81

Advertising
background image

The Auto Gen Start Menu

975-0082-01-01

3–33

Crank Retry Time

Purpose

“Crank Retry Time” specifies the length of time the Start relay is engaged
(and cranking the starter motor) for the second and subsequent attempts to
start the generator, in cases when the generator fails to start on the first
attempt.

When to use

This setting is automatically configured when you select a “Gen Type” for
your generator. You should manually set “Crank Retry Time” if you need
to customize your Gen Type on the advice of your generator manufacturer
or authorized service personnel.

Preheat Time

Purpose

“Preheat Time” specifies how long the Preheat relay is engaged during the
start sequence. The preheat signal may be required for diesel generators
with glow plugs or fuel priming for gas generators.

The Preheat relay may be Relay 1 or Relay 3, depending on the “Relay3”
setting or the Gen Type selected.

When to use

This setting is automatically configured when you select a “Gen Type” for
your generator. You should manually set “Preheat Time” if you need to
customize your Gen Type on the advice of your generator manufacturer or
authorized service personnel.

Values

Default

0s to 250s (increments of 1s)

40s

Values

Default

0s to 250s (increments of 1s)

0s