Type 3, Type 3 –12 – Xantrex Technology Automatic Generator User Manual

Page 34

Advertising
background image

Installation

2–12

975-0082-01-01

Type 3

Type 3 is a three-wire GlowStop with shutdown bypass configuration.
The configuration shown in Figure 2-5 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. (Generators with this functionality often
have a manual means of disabling it during cranking.)

Figure 2-5 Type 3 connection diagram

Table 2-4 Type 3 relay and timing preset configurations

Relay 1 mode

GlowStop/Shutdown bypass

Relay 3 mode

Preheat/Shutdown bypass

Gen Run signal hold time

0.5 s

Preheat time

20 s

Preheat to crank delay

0 s

Crank time

15 s

Crank retry time

30 s

Shutdown bypass time

10 s

Start tries

3

PREHEAT

BYPASS SHUTDOWN

STOP

14

13

12

GEN RUN SIGNAL
GROUND

18

17

START

16

Relay 1

Relay 2

5A fuse

5A fuse

Generator wire

AGS wiring harness wire

Complete overcurrent protection
not shown. Refer to page 2–6.