The Auto Gen Start Menu
975-0082-01-01
3–27
assured of a full charge if the generator runs until the charger reaches the 
Float stage, rather than waiting until the charger charges the batteries to 
the voltage you may have set for “StopBattV” (see page 3–22).
For more information on battery charging, see your inverter/charger 
guide.
Outcomes
If you enable the Auto Gen Start to stop the generator when the batteries 
have been charged to the Float stage, it will stop the generator if it has 
been started automatically by the Battery Voltage (“StartV:30sec”, 
“StartV:15min”, “StartV:2hr”, and “StartV:24hr”) or State of Charge 
settings.
If you do not set “Stop Float” to On, the Auto Gen Start will not stop the 
generator in response to the battery charging stage. The generator will 
stop in response to battery voltage (“StopBattV”) instead. In this case, 
ensure that the “StopBattV” is enabled and set at the correct voltage.