Installing the Auto Gen Start

975-0082-01-01

2–15

Type 6

Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact. This generator type is intended for Yamaha generators.

Type 7

Type 7 will work with both two-wire and three-wire run mode
configurations that require a preheat signal before cranking, such as
Generac Backup/Renewable generators. This Gen Type setting is suitable
for generators with an automatic engine cranking control system (two-
wire) and generators that require that the Auto Gen Start control their
starter separately (three-wire).

Figure 2-7 Type 6 connection diagram

Table 2-7 Type 6 relay and timing preset configurations

Relay 1 mode

GlowStop

Relay 3 mode

No function

Gen Run signal hold time

0.5 s

Preheat time

10 s

Preheat to crank delay

1 s

Crank time

15 s

Crank retry time

30 s

Shutdown bypass time

0 s

Start tries

3

18

17

START

16

15

13

12

GEN RUN SIGNAL

GROUND
PREHEAT

14

STOP

Relay 2

Relay 1

5A fuse

5A fuse

5A fuse

Generator wires

AGS wiring harness

Complete overcurrent protection
not shown. Refer to page 2–6.