A.4 attach the external relay module, Own in, Figure 77 – Hach-Lange SC 1000 User Manual

Page 147

Advertising
background image

145

A.4 Attach the external relay module

The external relay card provides 4 relays, each with one change-over contact. The relays
can switch maximum 250 VAC, 5 A (UL, SPDT-CO, change-over). They can be
programmed for limits, status, timers, and special functions.

1. Remove power and disconnect all cable connections to the module.

2. Place the external relay module on the DIN rail to the right of the base module and

slide firmly against the base module (or other connected modules).

3. Make the appropriate connections as shown in

Figure 78

and

Table 51

.

4. Connect cables to the module and reconnect power from the instrument.

Figure 77 External base module

Table 50 Base Module Terminal Assignments

Terminal

Terminal assignment

Description

1

+ 24 VDC

Power Supply (+)

2

Not used

3

0 V

Power Supply (–)

4

PE (Protective Earth)

Ground 24 V

5

+

For sc1000 network expansion, coming

6

For sc1000 network expansion, coming

7

Not used

8

PE (Protective Earth)

Ground network connection

9–12

Not used

13

+

For sc1000 network expansion, going

14

For sc1000 network expansion, going

15

Not used

16

PE (Protective Earth)

Ground network connection

Advertising