Table 7, Installation – Hach-Lange SC 1000 User Manual

Page 36

Advertising
background image

34

Installation

After installation and connection of a plug-in expansion card, the card must be configured
to the system. For Modbus card setup instructions, refer to

section 6.3.4.2, page 109

.

)

Figure 24 Modbus RS485 (YAB021) card connections

1

Card (Reverse side)

3

Jumper 1&2 unplugged for full duplex (4-wire)

2

Jumper 1&2 plugged for half duplex (2-wire)

4

Terminal block (Refer to

Table 7

for terminal

assignments)

Table 7 Modbus RS485 card (YAB021) terminal assignments

Terminal

Modbus RS485 designation with 4 wires

Modbus RS485 designation with 2 wires

1

Not Used

Not Used

2

Not Used

Not Used

3

Output –

4

Output +

+

5

Input –

6

Input +

+

7

Shield (connected to Protective Earth)

Shield (connected to Protective Earth)