3 relay menu, Advanced operations – Hach-Lange SC 1000 User Manual

Page 88

Advertising
background image

86

Advanced Operations

The output value (OV) is determined according to formula

(4)

:

where:
OV=Output value
IC=Input current
LV=Low value
HV=High value

6.3.3 Relay menu

Note: This menu appears only if a relay card is installed in the sc1000 controller.

The relay menu content for a relay card depends on the selected working mode. There
are several relay card working modes:

ALARM
Relay controls if a process value is between two limits.

Figure 54 Output value with an input range of 4

20 mA

1

Output value (concentration) (y-axis)

5

4 mA

2

OV=f(IC)

6

0 mA

3

Input current (x-axis)

7

Low value (LV)

4

20 mA

8

High value (HV)

(4)

OV

=

f(IC)

=

HV – LV

×

(IC – 4 mA)

+

LV

16 mA

Advertising