Eia-422 interface wiring, Wiring – Watlow Series 988 Family User Manual

Page 16

Advertising
background image

2.4

Data Communications with the Watlow Series 988 Family

Hardware and Wiring, Chapter 2

Wiring

EIA-422 Interface Wiring

The EIA-422 communications uses a five-wire, full-duplex system. There are two
separate lines for transmitting, two lines for receiving and a common line between
the computer and the controller. With EIA-422 you can connect from one to ten
controllers to a single computer.

This diagram is a typical wiring example for units shipped after 1993 (see

ç

Caution on this page). The connections to the converter box or computer may
vary, depending on the model. Refer to the documentation for specific information.

NOTE:
The Electronic
Industry Association
(EIA) RS-422
standard recom-
mends a maximum
network distance of
4,000 feet.

Figure 2.4 -
EIA-422 Interface
Wiring Diagrams.

Com

T-

T+

R-

R+

B'
A'

B
A

Gnd

Converter Box or Card

Controller #1

Com 7

R-

6

R+

5

T-

4

T+

3

T+

3

T-

4

R+

5

R-

6

Com 7

As many as 10 units
can be connected to
an EIA-422 network.

Controller #2

If the system does not work properly it may need
termination resistors across the receive A and B termi-
nals at the converter. A typical value would be 240

.

Pull-up and pull-down resistors may be needed to
maintain the correct voltage during the idle state.

+5V

Converter
box with
termination
pull-up and
pull-down
resistors.

B

A

B

A

RD

TD

1K

Gnd

1K

240

ç

CAUTION:
For older Series
986-989 control-
lers with a "date
code" of 4693 or
earlier, terminal
3 is T-, 4 is T+, 5
is R- and 6 is
R+. (See Diag-
nostics Menu in
the User's
Manual.)

T-

3

T+

4

R-

5

R+

6

Com 7

Controller