Temperature/process controller prompt table, Table 6.10, Pid2 to rh2 – Watlow Series 988 Family User Manual

Page 54

Advertising
background image

Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.10

Command Summary Series 986-989, Chapter 6

PID2

PID Set Crossover

? <sp> PID2 <cr>

0 = Process

101

Source Selection

= <sp> PID2 <sp> data.2 <cr>

1 = Set point
2 = None
Default: 0

PRC1

Process Range

? <sp> PRC1 <cr>

0 = 4-20mA

68

Output 1

= <sp> PRC1 <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRC2

Process Range

? <sp> PRC2 <cr>

0 = 4-20mA

71

Output 2

= <sp> PRC2 <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PRC3

Process Range

? <sp> PRC3 <cr>

0 = 4-20mA

91

Output 3

= <sp> PRC3 <sp> data.2 <cr>

1 = 0-20mA
2 = 0-5V

Î

(dc)

3 = 1-5V

Î

(dc)

4 = 0-10V

Î

(dc)

Default: 0

PROC Process Value for

? <sp> PROC <cr>

RL1 to RH1

102

PID A <-> B Switch

= <sp> PROC <sp> data.2 <cr>

Default: per IN1 and hardware

PWR

Percent Power

? <sp> PWR <cr>

-100% to 100%

6

Present Output

n/a

RA1A

Rate Output 1

? <sp> RA1A <cr>

0.00 to 9.99 minutes

23

PID Set A

= <sp> RA1A <sp> data.2 <cr>

Default: 0.00

RA1B

Rate Output 1

? <sp> RA1B <cr>

0.00 to 9.99 minutes

36

PID Set B

= <sp> RA1B <sp> data.2 <cr>

Default: 0.00

RA2A

Rate Output 2

? <sp> RA2A <cr>

0.00 to 9.99 minutes

29

PID Set A

= <sp> RA2A <sp> data.2 <cr>

Default: 0.00

RA2B

Rate Output 2

? <sp> RA2B <cr>

0.00 to 9.99 minutes

42

PID Set B

= <sp> RA2B <sp> data.2 <cr>

Default: 0.00

RE1A

Reset Output 1

? <sp> RE1A <cr>

if ALGO = 0, 1, or 3, then

22

PID Set A

= <sp> RE1A <sp> data.2 <cr>

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE1B

Reset Output 1

? <sp> RE1B <cr>

if ALGO = 0, 1, or 3, then

35

PID Set B

= <sp> RE1B <sp> data.2 <cr>

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE2A

Reset Output 2

? <sp> RE2A <cr>

if ALGO = 0, 1, or 3, then

28

PID Set A

= <sp> RE2A <sp> data.2 <cr>

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RE2B

Reset Output 2

? <sp> RE2B <cr>

if ALGO = 0, 1, or 3, then

41

PID Set B

= <sp> RE2B <sp> data.2 <cr>

0.00 to 9.99 repeats/min.
if ALGO = 2, then -100.0% to 100.0%
Default: 0.00 repeats/min. or 0.0%

RH1

Range High

? <sp> RH1 <cr>

min. IN1 range to to max. IN1 range

50

Input 1

= <sp> RH1 <sp> data.2 <cr>

Default: Sensor high range

RH2

Range High

? <sp> RH2 <cr>

min. IN2 range to to max. IN2 range

58

Input 2

= <sp> RH2 <sp> data.2 <cr>

Default: Sensor high range

Table 6.10 -

PID2 to RH2

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)