Ramping controller prompt table, Table 5.4, Anun to de1 – Watlow Series 988 Family User Manual

Page 32

Advertising
background image

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

Ramping Controller Prompt Table

981,

982,

983, 984

Data Communications with the Watlow Series 988 Family

Command Summary Series 981-984, Chapter 5

5.4

ANUN Alarm Annunciation ? <sp> ANUN <cr>

0 = off

725

= <sp> ANUN <sp> data.2 <cr>

1 = on
Default: on

AOUT Analog Output 3

? <sp> AOUT <cr>

0 = Retransmit Process Input 1

743

Retransmit Function = <sp> AOUT <sp> data.2 <cr>

1 = Retransmit Set Point 1
2 = off
3 = Retransmit Process Input 2
Default: 0

ARH

Retransmit

? <sp> ARH <cr>

ARL to 9999

745

Range High

= <sp> ARH <sp> data.2 <cr>

Default: RH1 or RH2 per AOUT

ARL

Retransmit

? <sp> ARL <cr>

-999 to ARH

744

Range Low

= <sp> ARL <sp> data.2 <cr>

Default: RL1 or RL2 per AOUT

ATSP

Auto-tune

? <sp> ATSP <cr>

50 to 150%

304

Set Point %

= <sp> ATSP <sp> data.2 <cr>

Default: 90%

AUT

Auto-tune

? <sp> AUT <cr>

0 = No auto-tuning

305

= <sp> AUT <sp> data.2 <cr>

1 = Tune PID
Default: off

C1

Input 1 Value

? <sp> C1 <cr>

Based on IN1 range ; RL1 to RH1

100

C2

Input 2 Value

? <sp> C2 <cr>

Based on IN2 range ; RL2 to RH2

104

CAL1

Input 1 Calibration

? <sp> CAL1 <cr>

-999°F to 999°F

605

Offset

= <sp> CAL1 <sp> data.2 <cr>

-555°C to 555°C
-999 units to 999 units
Default: 0

CAL2

Input 2 Calibration

? <sp> CAL2 <cr>

-999°F to 999°F

615

Offset

= <sp> CAL2 <sp> data.2 <cr>

-555°C to 555°C
-999 units to 999 units
Default: 0

CF

Degrees Select

? <sp> CF <cr>

0 = Display °F

901

Display Loop

= <sp> CF <sp> data.2 <cr>

1 = Display °C
Default: 0

CSP

Current Profile

? <sp> CSP <cr>

RL1 to RH1

1202

Set Point

CT1

Cycle Time

? <sp> CT1 <cr>

S.S. relay or open col:

506

Output 1

= <sp> CT1 <sp> data.2 <cr>

0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

CT2

Cycle Time

? <sp> CT2 <cr>

S.S. relay or open col:

516

Output 2

= <sp> CT2 <sp> data.2 <cr>

0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.

DATE

Factory Test Date

? <sp> DATE <cr>

xxyy

5

xx = week
yy = year

DB

Dead Band PID

? <sp> DB <cr>

-999°F to 999°F

505

Heat/Cool

= <sp> DB <sp> data.2 <cr>

-555°C to 555°C
-999 units to 999 units
Default: 0°F, 0°C, or 0 units

DE1

Derivative

? <sp> DE1 <cr>

0.00 to 9.99 minutes

503

Output 1 PID

= <sp> DE1 <sp> data.2 <cr>

Default: 0.00

Table 5.4 -

ANUN to DE1

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)