Temperature/process Controller Prompt Table

986, 987,

988

, 989

Data Communications with the Watlow Series 988 Family

6.3

Command Summary Series 986-989, Chapter 6

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

AMB

Ambient Terminal

? <sp> AMB <cr>

Input 1 terminals in 0.0

°

F

125

Temperature

ANUN Alarm Annunciation ? <sp> ANUN <cr>

0 = off

106

= <sp> ANUN <sp> data.2 <cr>

1 = on
Default: on

AOUT Analog Output 3

? <sp> AOUT <cr>

0 = Retransmit Process Output 1

90

Retransmit Function = <sp> AOUT <sp> data.2 <cr>

1 = Retransmit Set Point 1
2 = off
3 = Retransmit Process Output 2
Default: 0

ARH

Retransmit

? <sp> ARH <cr>

ARL to 9999

93

Range High

= <sp> ARH <sp> data.2 <cr>

Default: RH1 or RH2 per AOUT

ARL

Retransmit

? <sp> ARL <cr>

-999 to ARH

92

Range Low

= <sp> ARL <sp> data.2 <cr>

Default: RL1 or RL2 per AOUT

ATM

Auto-Manual Key

? <sp> ATM <cr>

0 = Auto mode

10

(Any data.2 toggles

= <sp> ATM <sp> data.2 <cr>

4 = Manual mode

ATM, like the pressing

Default: n/a

the AUTO/MAN key.)

Disabled if LOC = 2 or 3

AUT

Auto-tune

? <sp> AUT <cr>

0 = No auto-tuning

19

= <sp> AUT <sp> data.2 <cr>

1 = Tune PID Set A
2 = Tune PID Set B
Default: off

ATSP

Auto-tune

? <sp> ATSP <cr>

50 to 150%

109

Set Point %

= <sp> ATSP <sp> data.2 <cr>

Default: 90%

C1

Input 1 Value

? <sp> C1 <cr>

Based on IN1 range ; RL1 to RH1

1

C2

Input 2 Value

? <sp> C2 <cr>

Based on IN2 range ; RL2 to RH2

2

CAL

Lockout

? <sp> CAL <cr>

0 = No lockout

121

Calibration Menu

= <sp> CAL <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

CAL1

Input 1 Calibration

? <sp> CAL1 <cr>

-999 to 9999

51

Offset

= <sp> CAL1 <sp> data.2 <cr>

Default: 0

CAL2

Input 2 Calibration

? <sp> CAL2 <cr>

-999 to 9999

59

Offset

= <sp> CAL2 <sp> data.2 <cr>

Default: 0

CF

Degrees Select

? <sp> CF <cr>

0 = Display

°

F

95

Display Loop

= <sp> CF <sp> data.2 <cr>

1 = Display

°

C

Default = 0

CNTL

Control Function

? <sp> CNTL <cr>

0 = Normal

98

= <sp> CNTL <sp> data.2 <cr>

1 = Cascade
2 = Ratio
3 = Differential
Default = 0

COM

Lockout Comms

? <sp> COM <cr>

0 = No lockout

119

Menu

= <sp> COM <sp> data.2 <cr>

1 = Read only
2 = No read or write
Default: 0

CSAC Cascade Action

? <sp> CSAC <cr>

0 = direct action

99

= <sp> CSAC <sp> data.2 <cr>

1 = reverse action

Table 6.3 -

AMB to CSAC

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)