Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus

Address

996, 997,

998

, 999

Dual Channel Controller Prompt Table

Command Summary Series 996-999, Chapter 7

7.7

Data Communications with the Watlow Series 988 Family

IT1A

Integral for Output 1 ? <sp> IT1A <cr>

0.00 to 99.99 minutes per repeat

501

PID Channel A

= <sp> IT1A <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT1B

Integral for Output 1 ? <sp> IT1B <cr>

0.00 to 99.99 minutes per repeat

521

PID Channel B

= <sp> IT1B <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT2A

Integral for Output 2 ? <sp> IT2A <cr>

0.00 to 99.99 minutes per repeat

511

PID Channel A

= <sp> IT2A <sp> data.2 <cr>

Default: 0.00 minutes per repeat

IT2B

Integral for Output 2 ? <sp> IT2B <cr>

0.00 to 99.99 minutes per repeat

531

PID Channel B

= <sp> IT2B <sp> data.2 <cr>

Default: 0.00 minutes per repeat

ITY1

Input 1

? <sp> ITY1 <cr>

0 = None

8

Hardware Type

1 = t/c only
4 = Input off
5 = Universal RTD
6 = Universal high gain t/c
7 = Universal low gain t/c
8 = Universal millivolts
9 = Universal process

ITY2

Input 2

? <sp> ITY2 <cr>

0 = None

9

Hardware Type

1 = t/c only
4 = Input off
5 = Universal RTD
6 = Universal high gain t/c
7 = Universal low gain t/c
8 = Universal millivolts
9 = Universal process

LAT3

Alarm 3 Latching

? <sp> LAT3 <cr>

0 = Latching alarms

738

= <sp> LAT3 <sp> data.2 <cr>

1 = Non-latching alarms
Default: 1

LIN2

Linearization

? <sp> LIN2 <cr>

0 = None

618

Process Input 2

= <sp> LIN2 <sp> data.2 <cr>

1 = Wet bulb
2 = Vaisala HMM-30C
3 = Rotronic H260
Default: 0

LOC

Keyboard Lockout

? <sp> LOC <cr>

0 = No lockout

1300

= <sp> LOC <sp> data.2 <cr>

1 = Lock out mode key
2 = Lock out mode & auto/man keys
3 = Lock out all single keys
Default: 0

MDL

Model Number

? <sp> MDL <cr>

998 (996 - 999 dual channel unit)

0

MOD

Mode Key Action

= <sp> MOD <sp> 1 <cr>

0 = Mode to previous prompt

1900

1 = Mode to next prompt

OT1A

Output 1 Channel A

? <sp> OT1A <cr>

0 = Heat

700

Action

= <sp> OT1A <sp> data.2 <cr>

1 = Cool
2 = None

OT1B

Output 1 Channel B

? <sp> OT1B <cr>

0 = Heat

717

Action

= <sp> OT1B <sp> data.2 <cr>

1 = Cool
2 = None

OT2A

Output 2 Channel A

? <sp> OT2A <cr>

0 = Heat

716

Action

= <sp> OT2A <sp> data.2 <cr>

1 = Cool
2 = None

OT2B

Output 2 Channel B

? <sp> OT2B <cr>

0 = Heat

733

Action

= <sp> OT2B <sp> data.2 <cr>

1 = Cool
2 = None

OT3

Output 3 Action

? <sp> OT3 <cr>

0 = None

734

= <sp> OT3 <sp> data.2 <cr>

1 = Alarm 3
2 = Alarm 3 reverse acting

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

Table 7.7 -

IT1A to OT3

NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)