Temperature/process controller prompt table, Table 6.2, A2hi to alm – Watlow Series 988 Family User Manual

Page 46

Advertising
background image

Data Communications with the Watlow Series 988 Family

Temperature/process Controller Prompt Table

986, 987,

988

, 989

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

6.2

Command Summary Series 986-989, Chapter 6

Table 6.2 -

A2HI to ALM

ç

CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)

A2HI

Output 2 Alarm High ? <sp> A2HI <cr>

Process: A2LO to sensor high range

14

= <sp> A2HI <sp> data.2 <cr>

Deviation: 0 to 9999

°

Rate: 0 to 9999

°

/minute

Default: RH, 999

°

, or 999

°

/min.

A2LO

Output 2 Alarm Low ? <sp> A2LO <cr>

Process: sensor low range to A2HI

13

= <sp> A2LO <sp> data.2 <cr>

Deviation: -999 to 0

°

Rate: -9999 to 0

°

/minute

Default: RL, -999

°

, or -999

°

/min.

A3HI

Output 3 Alarm High ? <sp> A3HI<cr>

Process: A3LO to sensor high range

16

= <sp> A3HI <sp> data.2 <cr>

Deviation: 0 to 9999

°

Rate: 0 to 9999

°

/minute

Default: RH, 999

°

, or 999

°

/min.

A3LO

Output 3 Alarm Low ? <sp> A3LO <cr>

Process: sensor low range to A3HI

15

= <sp> A3LO <sp> data.2 <cr>

Deviation: -999 to 0

°

Rate: -999 to 0

°

/minute

Default: RL, -999

°

, or -999

°

/min.

ACAL Analog Offset

? <sp> ACAL <cr>

-999 to 999

°

F

94

= <sp> ACAL <sp> data.2 <cr>

-555 to 555

°

C

-999 to 999 units
Default: 0

°

F, 0

°

C, 0 units

AL2

Alarm 2 Type

? <sp> AL2 <cr>

0 = Deviation Alarm, Input 2

74

= <sp> AL2 <sp> data.2 <cr>

1 = Process Alarm, Input 2
2 = Process Alarm, Input 1
3 = Deviation Alarm, Input 1
4 = Rate Alarm, Input 1
Default: 2

AL3

Alarm 3 Type

? <sp> AL3 <cr>

0 = Deviation Alarm, Input 2

79

= <sp> AL3 <sp> data.2 <cr>

1 = Process Alarm, Input 2
2 = Process Alarm, Input 1
3 = Deviation Alarm, Input 1
4 = Rate Alarm, Input 1
Default: 2

ALGO Algorithm

? <sp> ALGO <cr>

0 = two sets of PID prompts [Pid2]

100

= <sp> ALGO <sp> data.2 <cr>

1 = one set of PID prompts [Pid]
2 = prop/derivative w/manual reset [Pdr]
3 = 1 process output both heat or cool [dUPL]
Default: 1

ALM

Alarm Status

? <sp> ALM <cr>

0 = No alarms occurring (0000 0000)

3

(Writing a 0 clears

= <sp> ALM <sp> 0 <cr>

Bit 1 = A2LO

(0000 0001)

next alarm.)

Bit 2 = A2HI

(0000 0010)

Bit 3 = A3LO

(0000 0100)

Bit 4 = A3HI

(0000 1000)

Advertising