Temperature/process Controller Prompt Table

986, 987,

988

, 989

Data Communications with the Watlow Series 988 Family

6.11

Command Summary Series 986-989, Chapter 6

Name

Description

Read (?) and/or Write (=) Syntax

Range

data.1

data.2

Modbus
address

RL1

Range Low

? <sp> RL1 <cr>

min. IN1 range to to max. IN1 range

49

Input 1

= <sp> RL1 <sp> data.2 <cr>

Default: Sensor low range

RL2

Range Low

? <sp> RL2 <cr>

min. IN2 range to to max. IN2 range

57

Input 2

= <sp> RL2 <sp> data.2 <cr>

Default: Sensor low range

RP

Ramping Initiation

? <sp> RP <cr>

0 = off

110

= <sp> RP <sp> data.2 <cr>

1 = on startup
2 = on startup and set point change
Default: 0

RSP

Remote Set Point

? <sp> RSP <cr>

0 = off

142

= <sp> RSP <sp> data.2 <cr>

1 = on
Default: 0

RATE

Ramp Rate

? <sp> RATE <cr>

0 to 9999

°

/minute

111

= <sp> RATE <sp> data.2 <cr>

Default: 100

°

/minute

RTD1

RTD Calibration

? <sp> RTD1 <cr>

0 = JIS

52

Curve Input 1

= <sp> RTD1 <sp> data.2 <cr>

1 = DIN
Default: 1

RTD2

RTD Calibration

? <sp> RTD2 <cr>

0 = JIS

60

Curve Input 2

= <sp> RTD2 <sp> data.2 <cr>

1 = DIN
Default: 1

SHYS

Slidewire

? <sp> SHYS <cr>

0 to HUNT

66

Hysteresis

= <sp> SHYS <sp> data.2 <cr>

SIL2

Alarm 2 Silence

? <sp> SIL2 <cr>

0 = off/disabled

77

= <sp> SIL2 <sp> data.2 <cr>

1 = on/enabled
Default: 0

SIL3

Alarm 3 Silence

? <sp> SIL3 <cr>

0 = off/disabled

83

= <sp> SIL3 <sp> data.2 <cr>

1 = on/enabled
Default: 0

SRNB Serial Number

? <sp> SRNB <cr>

xxxx = 0000 to 9999

124

Bottom Display
Read the six-digit unit
serial number in two
segments,
"SNxx" and "xxxx,"
i.e., as in the
upper and lower
front panel displays.

SRNT

Serial Number

? <sp> SRNT <cr>

SNxx = 00 to 99

123

Top Display

SOFT

Software Revision

? <sp> SOFT <cr>

0 = Rev A

7 = Rev H

14 = Rev O

141

1 = Rev B

8 = Rev I

15 = Rev P

2 = Rev C

9 = Rev J

16 = Rev Q

3 = Rev D

10 = Rev K

17 = Rev R

4 = Rev E

11 = Rev L

18 = Rev S

5 = Rev F

12 = Rev M

19 = Rev T

6 = Rev G

13 = Rev N

20 = Rev U
etc.

SP1

Set Point 1

? <sp> SP1 <cr>

RL1 to RH1, or

7

= <sp> SP1 <sp> data.2 <cr>

if CNTL = 2 (ratio), then 0.0 to 20.0
if CNTL = 3 (differential), then -999 to 999
if ATM = 1, then 0 to 100%
Default: per IN1 and hardware

Table 6.11 -

RL1 to SP1

ç

CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
(This does not
apply to Modbus
Protocol.)